Violation Details
                                                               
------------------------------------------------------
Facility Name:KALAMA STP
Permit:WA0020320
Category:85% Design Criteria Warning (if exceeded for 3 consecutive months triggers permit action)
Type:Design Criteria (85%)
Date: 10/1/2016
-
Notes: October 2016 - 85% TSS Design Exceedance: Exceedance was due to heavy rainfall.
---------------------------------------------------------
Monitoring Data
Parameter :Solids (Residue)
Fraction:Total suspended (TSS)
Units:Lbs/Day
Statistical Base:Average
Sample Type: Composite - 24 HR Time
Non Report Reason:-
BenchMark Min:-   Max:-
Limit Min:-   Max:-
Design: 992
Design Warning:843.2
Value:859.875
Violation Override: -
----------------------------------------------------
Related Enforcements
Enforcement ActionStatusDatePenalty AmountNotes
No enforcement action necessary Complete12/12/2016 October 2016 - 85% TSS Design Exceedance: Exceedance was due to heavy rainfall.