Violation Details
                                                               
------------------------------------------------------
Facility Name:LIBERTY LAKE SEWER & WATER DIST
Permit:WA0045144
Category:Exceedance of Design Criteria
Type:Design Criteria Exceedance
Date: 5/1/2020
-
Notes: NH3 exceeded Deign criteria for concentration and mass due to plant upset. Staff reported that nitrifying bacteria appeared to be affected by the increased use of sanitizers and cleaning agents due to the COVID -19 virus stay home order.
---------------------------------------------------------
Monitoring Data
Parameter :Ammonia
Fraction:Total
Units:Lbs/Day
Statistical Base:Seasonal Average
Sample Type: Composite - 24 HR Time
Non Report Reason:-
BenchMark Min:-   Max:-
Limit Min:-   Max:-
Design: 13.882
Design Warning:11.7997
Value:21.8
Violation Override: -
----------------------------------------------------
Related Enforcements
Enforcement ActionStatusDatePenalty AmountNotes
Informal Action - EmailComplete6/12/2020 NH3 exceeded Deign criteria for concentration and mass due to plant upset. Staff reported that nitrifying bacteria appeared to be affected by the increased use of sanitizers and cleaning agents due to the COVID -19 virus stay home order.