Violation Details
                                                               
------------------------------------------------------
Facility Name:King County South WWTP
Permit:WA0029581
Category:Numeric effluent violation
Type:Effluent Violations
Date: 6/10/2020
-
Notes: McKone: This is a tricky violation. The reported value is accurate and it exceeded the limit in the permit. However, I question whether the limit is appropriate for a short-duration, intermittent discharge. The reported value represented the average concentration discharged over 1.5 hrs into the Green River. Based on ambient sampling done at the time of this discharge, it did not appear to cause an exceedance of the water quality standard for the river.
---------------------------------------------------------
Monitoring Data
Parameter :Fecal Coliform
Fraction:Not Applicable
Units:#/100ml
Statistical Base:Single Sample (Main DMR Grid)
Sample Type: Grab
Non Report Reason:-
BenchMark Min:-   Max:-
Limit Min:-   Max:200
Design: -
Design Warning:-
Value:395
Violation Override: -
----------------------------------------------------
Related Enforcements
Enforcement ActionStatusDatePenalty AmountNotes
No enforcement action necessary Complete8/10/2020 Lipnickey: NFA as this was a short term action that did not affect the receiving waters.