Violation Details
                                                               
------------------------------------------------------
Facility Name:FAIRFIELD WWTP
Permit:WA0045489
Category:Numeric effluent violation
Type:Effluent Violations
Date: 2/1/2023
-
Notes: The TSS appeared very high in the 02/23 influent sampling. At this time we are unsure why TSS would be indicated as so high in the Influent sampling, we will be checking this and looking into what may have caused this. As well as ensuring we are doing everything, we can to maintain this at a lower reading moving forward. Ammonia Samples came back high in the first set of samples 02/14/23. This may have to do with the unusual weather patterns that we saw this February ranging from 4 degrees up to 46 degrees with inconsistent weather patterns of sun to snow. Waterfowl came and went this month. All of these factors could lead to pond turnover multiple times with in the month, the constant stirring of the ponds could potentially lead to a more septic like environment allowing for us to pick up more ammonia in sampling. We will continue to monitor this and act as necessary to prevent issues.
---------------------------------------------------------
Monitoring Data
Parameter :Ammonia
Fraction:Total
Units:Milligrams/L (mg/L)
Statistical Base:Average
Sample Type: Composite - 24 HR Time
Non Report Reason:-
BenchMark Min:-   Max:-
Limit Min:-   Max:2.3
Design: -
Design Warning:-
Value:3.65
Violation Override: -
----------------------------------------------------
Related Enforcements
Enforcement ActionStatusDatePenalty AmountNotes
Informal Action - EmailComplete4/6/2023 Ammonia Total 6.4mg/L (Max <= 4.6mg/L) - Ammonia Avg. 3.65mg/L ( Avg. <= 2.3mg/L) - Influent TSS Avg. 272.75 ( 212)
  • NoFilter
  • Contains
  • DoesNotContain
  • StartsWith
  • EndsWith
  • EqualTo
  • NotEqualTo
  • GreaterThan
  • LessThan
  • GreaterThanOrEqualTo
  • LessThanOrEqualTo
  • Between
  • NotBetween
  • IsEmpty
  • NotIsEmpty
  • IsNull
  • NotIsNull
  • Custom

The process of tracking how violations and triggers are addressed through the system is new to PARIS. All of the historical violations which were addressed will not have a related enforcement.