Violation Details
                                                               
------------------------------------------------------
Facility Name:
ROCKFORD WWTP
Permit:
WA0044831
Category:
Numeric effluent violation
Type:
Effluent Violations
Date:
4/23/2025
-
Notes:
---------------------------------------------------------
Monitoring Data
Parameter :
pH (Hydrogen Ion)
Fraction:
Not Applicable
Units:
Standard Units
Statistical Base:
Single Sample (Main DMR Grid)
Sample Type:
Grab
Non Report Reason:
-
BenchMark Min:
-
  Max:
-
Limit Min:
6.5
  Max:
8.5
Design:
-
Design Warning:
-
Value:
8.9
Violation Override:
-
----------------------------------------------------
Related Enforcements
Enforcement Action
Status
Date
Penalty Amount
Notes
No enforcement action necessary
Complete
5/16/2025
Draining down lagoon more than usual, into solids layer, in order to perform maintenance on lower drain pipe. Effluent TSS and BOD very high causing % removal, weekly and monthly violations. Draining later in the year than usual as well, causing daily pH violations for 2 weeks.