Planters Hotel
Facility Site ID:
8639
Cleanup Site ID:
12922
In the spring of 2015, two underground storage tanks (USTs) were removed from the Site. At that time, the Site contained a commercial building that was used as a fast food restaurant. The tanks were believed to have been used to store heating oil for a hotel that was demolished 45 years ago.
Tank 1 was capable of storing 3800 gallons and contained about 600 gallons of heavy heating oil upon discovery. The tank had several holes in the bottom and lower sides of the tank.
Tank 2 was about 1100 gallons and had approximately 200 gallons of liquid, which appeared to be water with minimal concentrations of petroleum. No obvious holes were found in the tank and no release was observed in the soil around this tank.
Three soil samples were collected from the bottom of each tank. All samples returned from the Tank 2 location were below MTCA Method A cleanup levels. The soil around Tank 1, however, was found to have diesel, heavy oil, total naphthalenes, and total cPAHs exceeding cleanup standards.
Groundwater was not encountered during tank excavation activities.
Tank 1 was capable of storing 3800 gallons and contained about 600 gallons of heavy heating oil upon discovery. The tank had several holes in the bottom and lower sides of the tank.
Tank 2 was about 1100 gallons and had approximately 200 gallons of liquid, which appeared to be water with minimal concentrations of petroleum. No obvious holes were found in the tank and no release was observed in the soil around this tank.
Three soil samples were collected from the bottom of each tank. All samples returned from the Tank 2 location were below MTCA Method A cleanup levels. The soil around Tank 1, however, was found to have diesel, heavy oil, total naphthalenes, and total cPAHs exceeding cleanup standards.
Groundwater was not encountered during tank excavation activities.
Voluntary Cleanup Program
This site is in our Voluntary Cleanup Program, which provides technical help to owners of contaminated sites.
Voluntary Cleanup Program customers pay fees to cover our costs for technical help and reviewing cleanup reports. Sites in this program must meet the same cleanup standards as sites Ecology manages under legal orders.
Documents 10
Legal 1
Document Title | Document Date | Document Type |
Planters Hotel (aka Future Papa Murphys) - Early Notice Letter | 12/4/2015 | Early Notice Letter |
Technical Reports 7
Document Title | Document Date | Document Type |
Planters Hotel - Compliance Monitoring Plan | 8/29/2023 | Site Specific Technical Document - other |
Planters Hotel - Cleanup Action Completion Report | 8/18/2023 | Final Cleanup Action Report |
Planters Hotel - Focused Feasibility Study | 3/11/2022 | Feasibility Study |
Planters Hotel - Investigation Report 2021 | 6/30/2021 | Site Specific Technical Document - other |
Planters Hotel - Supplemental Investigation Memo | 6/15/2021 | Site Specific Technical Document - other |
Planters Hotel - Soil and Groundwater Assessment | 6/26/2019 | Site Specific Technical Document - other |
Planters Hotel - UST Decommissioning and Site Assessment | 8/3/2015 | Site Specific Technical Document - other |
Voluntary Cleanup Program 2
Document Title | Document Date | Document Type |
Planters Hotel - Consultant Change of Contact forms | 8/22/2023 | VCP Administrative Document |
Planters Hotel - VCP application forms and acceptance letter | 3/18/2022 | VCP Administrative Document |
There may be more documents related to this site. To obtain documents not available electronically, you will need to make a public records request.
Places to see print documents
-
Central Regional Office1250 W Alder StUnion Gap, 98903-0009Please schedule an appointment to view print documents at this location.
Contaminants 6
Contaminant Type | Soil |
Groundwater |
Surface Water |
Air |
Sediment |
Bedrock |
---|---|---|---|---|---|---|
Non-Halogenated Organics - Non-Halogenated Solvents | C | B | ||||
Non-Halogenated Organics - Polycyclic Aromatic Hydrocarbons | C | C | ||||
Non-Halogenated Organics - Benzene | C | B | ||||
Non-Halogenated Organics - Petroleum-Diesel | C | C | ||||
Non-Halogenated Organics - Petroleum-Gasoline | C | B | ||||
Non-Halogenated Organics - Petroleum-Other | C | C |
- S
- Suspected
- C
- Confirmed Above Cleanup Levels
- B
- Below Cleanup Levels
- RA
- Remediated-Above
- RB
- Remediated-Below
- R
- Remediated
This contaminant list was based on our best information at the time it was entered. It may not reflect current conditions at the site.